BACnetStack_SetIntrinsicChangeOfStateAlgorithmBool
bool BACnetStack_SetIntrinsicChangeOfStateAlgorithmBool( const uint32_t deviceInstance, const uint16_t objectType, const uint32_t objectInstance, const bool alarmValue, const uint32_t timeDelay, const bool useTimeDelayNormal, const uint32_t timeDelayNormal, const bool enable);Enables the Intrinsic Change of State Algorithm with a BOOLEAN primitive for an object.
The object must exist and have alarms and events enabled by BACnetStack_SetAlarmsAndEventsForObjectEnabled(…, enabled=true) - an Event Enrollment object carries its own and needs no such call; otherwise this returns false.
This function will enable the required properties and store the initial values in memory.
BACnet reference: ANSI/ASHRAE 135-2024 clause 13.3.2 (CHANGE_OF_STATE Event Algorithm).
Parameters
Section titled “Parameters”| Parameter | Direction | Description |
|---|---|---|
deviceInstance |
in | The instance number of the device that owns this object. |
objectType, objectInstance |
in | The object for alarms and events: one BACnet Object Identifier, carried as two parameters (see the API conventions). |
alarmValue |
in | The BOOLEAN Present_Value that puts the object into OFFNORMAL (135-2024 cl. 13.3.2 pAlarmValues). On a Binary Input or Binary Value it is stored as BACnetBinaryPV (true = active, false = inactive). Each call REPLACES the previous alarm value (on an Event Enrollment, the whole alarm-value list), so calling it again with the other value re-arms the object on that value. |
timeDelay |
in | How long, in seconds, an offnormal condition has to persist before the event state changes to offnormal. |
useTimeDelayNormal |
in | Whether to use a different time delay value for the timeDelayNormal, or just use the timeDelay value. |
timeDelayNormal |
in | How long, in seconds, a normal condition has to persist before the event state returns to normal. |
enable |
in | Initial inhibit state, inverted - NOT a remove. true arms the algorithm; false leaves it armed but INHIBITED through the object’s Event_Algorithm_Inhibit property (or Reliability_Evaluation_Inhibit for a fault algorithm). Both of those properties are made WRITABLE by BACnetStack_SetAlarmsAndEventsForObjectEnabled(), so a remote client can change the state afterwards. To genuinely remove an armed algorithm, disable the object with BACnetStack_SetAlarmsAndEventsForObjectEnabled(…, enabled=false). Recommended value: true |
Returns
Section titled “Returns”True on success; false if the device or object does not exist, the object type does not support this algorithm, or Alarm-and-Event support was not compiled (STACK_OPTION_ALARMS_AND_EVENTS).
Topic: Alarms and events. Declared in CASBACnetStackDLL.h.