Positive Integer Value

A Positive Integer Value object holds a whole number that is zero or greater, with engineering units. Use it for counts, ratings and other values that are never negative and can be larger than a small state number. Clients read it and, if the device allows, write it.

  • Run-time hours of equipment
  • Number of occupants in a room
  • Target speed in rpm
  • Event or start counter
  • Rated capacity of a unit
Property What it holds
Present_Value The unsigned whole number the object holds.
Units The engineering units of the value.
COV_Increment How far Present_Value must move before a subscribed client is notified. Present only when the object supports COV.
Priority_Array Optional. Present only when the value is commandable; sixteen priority slots.
Low_Limit / High_Limit Optional limits for alarms. The object reports off-normal when the value passes one, after the time delay.

The object is commandable only if you give it a priority array. When it reports intrinsic events, the standard pairs it with the UNSIGNED_OUT_OF_RANGE algorithm, which has a deadband for the return to normal. COV notifications go out when Present_Value changes by COV_Increment or on any change to Status_Flags.

Enable it with the STACK_OPTION_OBJECT_TYPE_POSITIVE_INTEGER_VALUE build option and add each object with BACnetStack_AddObject. Serve Present_Value with the callback you register with BACnetStack_RegisterCallbackGetPropertyUnsignedInteger and, if clients may write it, the BACnetStack_RegisterCallbackSetPropertyUnsignedInteger callback. The object becomes commandable once you enable both PriorityArray and RelinquishDefault. To arm alarms, enable alarms for the object and call BACnetStack_SetIntrinsicUnsignedOutOfRangeAlgorithm; do not use BACnetStack_SetIntrinsicUnsignedRangeAlgorithm, which is the no-deadband variant meant for other types. Call BACnetStack_UpdateValue whenever the value you serve changes, so COV, trend logs and alarms see it. The stack has no fault out-of-range setter for this type: BACnetStack_SetFaultOutOfRangeAlgorithmReal refuses it.

Integer Value, Analog Value, Accumulator

The properties ASHRAE 135-2024 clause 12.44 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Description CharacterString O no no ""
Present_Value Unsigned R1 yes no (yes while Out_Of_Service is true) No default: value-not-initialized. Once Priority_Array and Relinquish_Default are enabled, built by the stack from the priority array your callbacks serve.
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Event_State BACnetEventState O4 no no 0
Reliability BACnetReliability O no no (yes while Out_Of_Service is true) 0
Out_Of_Service Boolean O no no false
Units BACnetEngineeringUnits R yes no 95 (no units)
Priority_Array BACnetARRAY[16] of BACnetOptionalUnsigned O2 no no Built by the stack from your callbacks.
Relinquish_Default Unsigned O2 no no No default: value-not-initialized until a callback or a client write supplies one.
COV_Increment Unsigned O3 no no 0
Time_Delay Unsigned O4,6 no no 0
Notification_Class Unsigned O4,6 no no 0
High_Limit Unsigned O4,6 no no 0
Low_Limit Unsigned O4,6 no no 0
Deadband Unsigned O4,6 no no 0
Limit_Enable BACnetLimitEnable O4,6 no no An empty bit string.
Event_Enable BACnetEventTransitionBits O4,6 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O4,6 no no An empty bit string.
Notify_Type BACnetNotifyType O4,6 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O4,6 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O6 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O6 no no ""
Event_Detection_Enable Boolean O4,6 no no false
Event_Algorithm_Inhibit_Ref BACnetObjectPropertyReference O6 no no No default: the read fails.
Event_Algorithm_Inhibit Boolean O6,7 no no false
Time_Delay_Normal Unsigned O6 no no 0
Reliability_Evaluation_Inhibit Boolean O8 no no false
Min_Pres_Value Unsigned O no no 0
Max_Pres_Value Unsigned O no no 0
Resolution Unsigned O no no 0
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Fault_High_Limit Unsigned O9 no no 0
Fault_Low_Limit Unsigned O9 no no 0
Current_Command_Priority BACnetOptionalUnsigned O2 no no Built by the stack from your callbacks.
Value_Source BACnetValueSource O10,12,14 no no No default: the read fails.
Value_Source_Array BACnetARRAY[16] of BACnetValueSource O11,13 no no No default: the read fails.
Last_Command_Time BACnetTimeStamp O11,13 no no No default: the read fails.
Command_Time_Array BACnetARRAY[16] of BACnetTimeStamp O13 no no No default: the read fails.
Audit_Level BACnetAuditLevel O15 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O15 not in profile not in profile No default: the read fails.
Audit_Priority_Filter BACnetOptionalPriorityFilter O15 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""