BACnetStack_SetTrendLogTypeToTriggered

bool BACnetStack_SetTrendLogTypeToTriggered(
const uint32_t deviceInstance,
const uint16_t objectType,
const uint32_t objectInstance,
const bool enable,
const bool stopWhenFull);

Sets property values of an existing Trend Log object or Trend Log Multiple Object.

This function should only be called after the AddTrendLogObject or AddTrendLogMultipleObject functions.

This function sets the log object to used the trigger type of logging and users can specify some parameters like if it should be enabled and if logging should stop when full.

Trigger logging occurs when a BACnet client writes to the Trigger property to set it to true. After taking a log, the Trigger property is reset to false

BACnet reference: ANSI/ASHRAE 135-2024 clause 12.25 (Trend Log Object Type).

Parameter Direction Description
deviceInstance in The instance of the device that contains the Trend Log object.
objectType in The type of trend log object. Must be either BACnetObjectType::trendLog or BACnetObjectType::trendLogMultiple. With objectInstance, this is one BACnet Object Identifier carried as two parameters (see the API conventions).
objectInstance in The instance of the Trend Log object to update.
enable in Whether to enable logging on the Trend Log object (true) or not (false).
stopWhenFull in Whether to stop logging when the log buffer is full (true) or not (false).

True if successful, otherwise false.

Topic: Schedules, calendars, trend logs and other object configuration. Declared in CASBACnetStackDLL.h.