Skip to content
Version 6.1.0
Contact Us

Averaging

An Averaging object samples one property over a sliding time window and reports the minimum, maximum and average. It turns a noisy reading into a smoothed one without extra programming. It can sample a property on its own device or, optionally, one on another device.

  • A 15-minute average of electrical demand
  • The peak temperature over the last hour
  • A smoothed pressure reading for a control loop
  • The lowest flow rate in the last shift
Property What it holds
Object_Property_Reference The property being sampled. It can be Boolean, integer, unsigned, enumerated or real.
Window_Interval The length of the sliding window, in seconds.
Window_Samples How many samples the window holds. A new sample is taken every interval divided by this count.
Minimum_Value The smallest sample in the window.
Maximum_Value The largest sample in the window.
Average_Value The mean of the valid samples in the window.

The object is not commandable and the standard defines no event algorithm for it. Valid_Samples and Attempted_Samples show how full the window is and how many reads failed.

Enable it with the STACK_OPTION_OBJECT_TYPE_AVERAGING build option and add each object with BACnetStack_AddObject. The stack serves the object identifier, type and property list; you provide the rest through your property callbacks.

Analog Input, Analog Value, Trend Log

The properties ASHRAE 135-2024 clause 12.5 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Minimum_Value Real R yes no 0.0
Minimum_Value_Timestamp BACnetDateTime O not in profile not in profile No default: the read fails.
Average_Value Real R yes no 0.0
Variance_Value Real O no no 0.0
Maximum_Value Real R yes no 0.0
Maximum_Value_Timestamp BACnetDateTime O not in profile not in profile No default: the read fails.
Description CharacterString O no no ""
Attempted_Samples Unsigned W1 yes yes 0
Valid_Samples Unsigned R yes no 0
Object_Property_Reference BACnetDeviceObjectPropertyReference R1 yes no No default: the read fails.
Window_Interval Unsigned W1 yes yes 0
Window_Samples Unsigned W1 yes yes 0
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Audit_Level BACnetAuditLevel O2 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O2 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""