Load Control
A Load Control object lets a utility, a demand-response system or another controller ask a device to shed electrical load for a set time. The device decides how to shed; the client only sees whether it is complying. It suits building controllers that take part in demand response.
Typical uses
Section titled “Typical uses”- Shed 20 percent of a building’s load during a peak event
- Let a utility gateway start a demand-response event
- Schedule a shed for a later start time
- Report whether the building met the requested shed
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Present_Value | The shed state: inactive, request pending, compliant or non-compliant. |
| Requested_Shed_Level | How much to shed, as a percent, an amount or a level. |
| Start_Time | When the shed should begin. Writing it starts a request. |
| Shed_Duration | How long the shed lasts, in minutes. |
| Expected_Shed_Level | The level the object expects to reach for the pending or active request. |
| Actual_Shed_Level | The level currently achieved. |
How it behaves
Section titled “How it behaves”Present_Value follows a state machine as requests arrive, start, finish or cannot be met. The object keeps its request across a restart. The standard pairs it with the CHANGE_OF_STATE algorithm on Present_Value. It also sends change-of-value notices for Present_Value.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_LOAD_CONTROL build option and add each object with BACnetStack_AddObject. Arm change-of-state alarms with BACnetStack_SetAlarmsAndEventsForObjectEnabled and then BACnetStack_SetIntrinsicChangeOfStateAlgorithmEnum; the alarm values are shed states. CASBACnetStackDLL.h declares no function that is specific to Load Control.
Related object types
Section titled “Related object types”Schedule, Command, Notification Class
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.28 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Description | CharacterString | O | no | no | "" |
| Present_Value | BACnetShedState | R | yes | no | No default: value-not-initialized. |
| State_Description | CharacterString | O | no | no | "" |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | R | yes | no | 0 |
| Reliability | BACnetReliability | O | no | no | 0 |
| Requested_Shed_Level | BACnetShedLevel | W | yes | yes | No default: the read fails. |
| Start_Time | BACnetDateTime | W | yes | yes | No default: the read fails. |
| Shed_Duration | Unsigned | W | yes | yes | 0 |
| Duty_Window | Unsigned | W | yes | yes | 0 |
| Enable | Boolean | W | yes | yes | false |
| Full_Duty_Baseline | Real | O | no | no | 0.0 |
| Expected_Shed_Level | BACnetShedLevel | R | yes | no | No default: the read fails. |
| Actual_Shed_Level | BACnetShedLevel | R | yes | no | No default: the read fails. |
| Shed_Levels | BACnetARRAY[N] of Unsigned | W1 | yes | yes | 0 |
| Shed_Level_Descriptions | BACnetARRAY[N] of CharacterString | R | yes | no | "" |
| Notification_Class | Unsigned | O2,4 | no | no | 0 |
| Time_Delay | Unsigned | O2,4 | no | no | 0 |
| Event_Enable | BACnetEventTransitionBits | O2,4 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O2,4 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O2,4 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O2,4 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O4 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O4 | no | no | "" |
| Event_Detection_Enable | Boolean | O2,4 | no | no | false |
| Event_Algorithm_Inhibit_Ref | BACnetObjectPropertyReference | O4 | no | no | No default: the read fails. |
| Event_Algorithm_Inhibit | Boolean | O4,5 | no | no | false |
| Time_Delay_Normal | Unsigned | O4 | no | no | 0 |
| Reliability_Evaluation_Inhibit | Boolean | O6 | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Value_Source | BACnetValueSource | O7,8,9 | no | no | No default: the read fails. |
| Audit_Level | BACnetAuditLevel | O10 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O10 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |