Life Safety Zone

A Life Safety Zone object groups Life Safety Point objects and other zones into one area, such as a floor or a fire compartment. It reports one combined life-safety state for the area. A safety panel exposes zones so an operator can see and silence a whole area at once.

  • Show the alarm state of a whole floor
  • Silence all horns in a fire compartment
  • Group smoke detectors by area
  • Report a zone in test mode
Property What it holds
Present_Value The zone’s life-safety state, such as quiet, pre-alarm or alarm. It may stay latched until reset.
Zone_Members The points and zones in this zone, as object references.
Mode The operating mode of the zone. Accepted_Modes lists the modes it allows.
Silenced Whether the zone’s signals are silenced.
Operation_Expected The next operation the zone expects, such as reset or silence.

The zone is not commandable; clients act on it through the LifeSafetyOperation service and by writing Mode. Where it reports events itself, the standard pairs it with the CHANGE_OF_LIFE_SAFETY algorithm, which uses the alarm value lists, the Mode and Operation_Expected. A fault algorithm can set Reliability from Fault_Values.

Enable it with the STACK_OPTION_OBJECT_TYPE_LIFE_SAFETY_ZONE build option and add each object with BACnetStack_AddObject. Serve Present_Value with the callback you register with BACnetStack_RegisterCallbackGetPropertyEnumerated and the BACnetStack_RegisterCallbackSetPropertyEnumerated callback, and Object_Name with the BACnetStack_RegisterCallbackGetPropertyCharacterString callback. Handle silence and reset requests with BACnetStack_RegisterCallbackLifeSafetyOperation. Arm alarms with BACnetStack_SetAlarmsAndEventsForObjectEnabled, then BACnetStack_SetIntrinsicChangeOfLifeSafetyAlgorithm, and add BACnetStack_SetFaultLifeSafetyAlgorithm for fault values.

Life Safety Point, Notification Class, Structured View

The properties ASHRAE 135-2024 clause 12.16 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Present_Value BACnetLifeSafetyState R yes no No default: value-not-initialized.
Tracking_Value BACnetLifeSafetyState R1 yes no (yes while Out_Of_Service is true) 0
Description CharacterString O no no ""
Device_Type CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Event_State BACnetEventState R yes no 0
Reliability BACnetReliability R1 yes no (yes while Out_Of_Service is true) 0
Out_Of_Service Boolean R yes no false
Mode BACnetLifeSafetyMode W yes yes 0
Accepted_Modes BACnetLIST of BACnetLifeSafetyMode R yes no 0
Time_Delay Unsigned O2,4 no no 0
Notification_Class Unsigned O2,4 no no 0
Life_Safety_Alarm_Values BACnetLIST of BACnetLifeSafetyState O2,4 no no 0
Alarm_Values BACnetLIST of BACnetLifeSafetyState O2,4 no no 0
Fault_Values BACnetLIST of BACnetLifeSafetyState O no no 0
Event_Enable BACnetEventTransitionBits O2,4 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O2,4 no no An empty bit string.
Notify_Type BACnetNotifyType O2,4 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O2,4 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O4 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O4 no no ""
Event_Detection_Enable Boolean O2,4 no no false
Event_Algorithm_Inhibit_Ref BACnetObjectPropertyReference O4 no no No default: the read fails.
Event_Algorithm_Inhibit Boolean O4,5 no no false
Time_Delay_Normal Unsigned O4 no no 0
Reliability_Evaluation_Inhibit Boolean O no no false
Silenced BACnetSilencedState R yes no 0
Operation_Expected BACnetLifeSafetyOperation R yes no 0
Maintenance_Required Boolean O no no false
Zone_Members BACnetLIST of BACnetDeviceObjectReference R yes no No default: the read fails.
Member_Of BACnetLIST of BACnetDeviceObjectReference O no no No default: the read fails.
Floor_Number Unsigned8 O no no 0
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Value_Source BACnetValueSource O6,7,8 no no No default: the read fails.
Audit_Level BACnetAuditLevel O9 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O9 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""