Trend Log
A Trend Log object records the history of one property of one object. It stores timestamped readings in a circular buffer that clients read back later with ReadRange. Use it to keep a record of a value even when no workstation is online to collect it.
Typical uses
Section titled “Typical uses”- Room temperature history
- Energy meter readings at fixed intervals
- Changes in a status or setpoint
- Trigger-based snapshots on demand
- Data a front end pulls overnight
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Log_DeviceObjectProperty | The object and property being logged. |
| Logging_Type | How readings are taken: at a set interval (polled), when the value changes by an amount (COV), or when a client triggers one. |
| Log_Buffer | The stored records. A client reads them with ReadRange, not ReadProperty. |
| Buffer_Size | The most records the buffer holds. Once full, the oldest are overwritten unless Stop_When_Full is set. |
| Total_Record_Count | How many records have ever been logged. Clients use it to see what is new. |
| Enable | Switches logging on or off. Start_Time and Stop_Time can also bound it. |
How it behaves
Section titled “How it behaves”The object is not commandable. When it reports intrinsic events, the standard pairs it with the BUFFER_READY algorithm, which notifies a client once a chosen number of new records has been logged since the last notice. The Client_COV_Increment property sets how large a change triggers a COV-type record.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_T_VMT_TRENDING_VIEWING_AND_MODIFYING_TRENDS build option, which also enables STACK_OPTION_OBJECT_TYPE_TREND_LOG. Do not use BACnetStack_AddObject: add the object with BACnetStack_AddTrendLogObject, giving the logged object and property and the buffer size. Then choose the logging type with BACnetStack_SetTrendLogTypeToPolled, BACnetStack_SetTrendLogTypeToCOV or BACnetStack_SetTrendLogTypeToTriggered, and bound it with BACnetStack_SetTrendLogStartStopTime. The stack stores the logging properties itself, so a callback cannot override them. Register BACnetStack_RegisterCallbackGetSystemTime, or writes to the object abort. Logging a property held by another device is not supported. Add and read records with BACnetStack_InsertTrendLogRecord and BACnetStack_ReadTrendLogRecord. For BUFFER_READY, enable alarms and call BACnetStack_SetIntrinsicBufferReadyAlgorithm.
Related object types
Section titled “Related object types”Trend Log Multiple, Event Log, Analog Input
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.25 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Description | CharacterString | O | no | no | "" |
| Enable | Boolean | W | yes | yes | Held by the stack. |
| Start_Time | BACnetDateTime | O1,2 | no | yes | Held by the stack. |
| Stop_Time | BACnetDateTime | O1,2 | no | yes | Held by the stack. |
| Log_DeviceObjectProperty | BACnetDeviceObjectPropertyReference | O8 | no | no | Held by the stack. |
| Log_Interval | Unsigned | O1,3 | no | yes | Held by the stack. |
| COV_Resubscription_Interval | Unsigned | O | no | no | 0 |
| Client_COV_Increment | BACnetClientCOV | O | no | no | Held by the stack. |
| Stop_When_Full | Boolean | R | yes | no | Held by the stack. |
| Buffer_Size | Unsigned32 | R | yes | no | Held by the stack. |
| Log_Buffer | BACnetLIST of BACnetLogRecord | R | yes | no | Held by the stack. Read it with ReadRange; a ReadProperty is refused. |
| Record_Count | Unsigned32 | W | yes | yes | Held by the stack. |
| Total_Record_Count | Unsigned32 | R | yes | no | Held by the stack. |
| Logging_Type | BACnetLoggingType | R | yes | no | Held by the stack. |
| Align_Intervals | Boolean | O5 | no | yes | false |
| Interval_Offset | Unsigned | O5 | no | yes | 0 |
| Trigger | Boolean | O | no | no | Held by the stack. |
| Status_Flags | BACnetStatusFlags | R | yes | no | Held by the stack. |
| Reliability | BACnetReliability | O | no | no | 0 |
| Notification_Threshold | Unsigned32 | O4,7 | no | no | 0 |
| Records_Since_Notification | Unsigned32 | O4,7 | no | no | 0 |
| Last_Notify_Record | Unsigned32 | O4,7 | no | no | 0 |
| Event_State | BACnetEventState | R | yes | no | NORMAL, or the alarm engine’s state once alarms are enabled. |
| Notification_Class | Unsigned | O4,7 | no | no | 0 |
| Event_Enable | BACnetEventTransitionBits | O4,7 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O4,7 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O4,7 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O4,7 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O7 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O7 | no | no | "" |
| Event_Detection_Enable | Boolean | O4,7 | no | no | false |
| Event_Algorithm_Inhibit_Ref | BACnetObjectPropertyReference | O7 | no | no | No default: the read fails. |
| Event_Algorithm_Inhibit | Boolean | O7,9 | no | no | false |
| Reliability_Evaluation_Inhibit | Boolean | O10 | no | no | false |
| Audit_Level | BACnetAuditLevel | O11 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O11 | not in profile | not in profile | No default: the read fails. |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |