Audit Reporter

An Audit Reporter object holds a device’s audit settings. A device that reports auditable actions needs at least one. It says which actions are reported, to whom, and how important they must be to be sent.

  • Reporting every property write to a central log
  • Auditing only object creation and deletion
  • Sending audit notices as confirmed messages
  • Limiting audit traffic by priority
Property What it holds
Audit_Level Sets how much of the device’s activity the reporter audits.
Auditable_Operations Which operations can be audited by this reporter.
Audit_Priority_Filter The command priorities whose writes are audited, one bit per priority from 1 to 16.
Issue_Confirmed_Notifications Chooses between confirmed and unconfirmed audit notices.
Monitored_Objects The objects, or whole object types, this reporter covers. If two reporters cover an object, the one with the lower instance reports it.
Send_Now A client writes it to push out any notices that are waiting.

The object may report its own fault conditions, but it applies no event algorithm and no standard fault algorithm.

Enable it with the STACK_OPTION_OBJECT_TYPE_AUDIT_REPORTER build option. Add each object with BACnetStack_AddObject. You serve its properties through your property callbacks.

Audit Log, Notification Class, Device

The properties ASHRAE 135-2024 clause 12.63 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Description CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Reliability BACnetReliability R yes no 0
Event_State BACnetEventState R yes no 0
Audit_Level BACnetAuditLevel R yes no 0
Audit_Source_Reporter Boolean R yes no false
Auditable_Operations BACnetAuditOperationFlags R yes no An empty bit string.
Audit_Priority_Filter BACnetPriorityFilter R yes no An empty bit string.
Issue_Confirmed_Notifications Boolean R yes no false
Monitored_Objects BACnetARRAY[N] of BACnetObjectSelector O no no No default: the read fails.
Maximum_Send_Delay Unsigned O1,2 no yes 0
Send_Now Boolean O1,2 no yes false
Event_Detection_Enable Boolean O3,5 no no false
Notification_Class Unsigned O3,5 no no 0
Event_Enable BACnetEventTransitionBits O3,5 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O3,5 no no An empty bit string.
Notify_Type BACnetNotifyType O3,5 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O3,5 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O4,5 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O5 no no ""
Reliability_Evaluation_Inhibit Boolean O no no false
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""