Access Zone
An Access Zone object represents a secured area. People enter through entry Access Points and leave through exit Access Points. The zone can count how many are inside and track who they are.
Typical uses
Section titled “Typical uses”- A laboratory with a maximum head count
- A parking area that counts vehicles in and out
- A ‘who is inside’ list for an evacuation roll call
- A zone that blocks re-entry with the same card
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Occupancy_State | Summarises the zone against its limits, for example below the lower limit or at the upper limit. |
| Occupancy_Count | How many people the zone currently holds, when counting is enabled. |
| Occupancy_Upper_Limit | The count at which the zone is considered full. |
| Credentials_In_Zone | The credentials currently inside. This is the ‘who is in’ list. |
| Entry_Points | The Access Point objects people use to enter. |
| Exit_Points | The Access Point objects people use to leave. |
How it behaves
Section titled “How it behaves”Intrinsic reporting is based on Occupancy_State and uses the CHANGE_OF_STATE algorithm, so a client can be notified when the zone moves into a limit state.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_ACCESS_ZONE build option and add each object with BACnetStack_AddObject. Property values come from your callbacks. Arm the alarm with BACnetStack_SetAlarmsAndEventsForObjectEnabled and then BACnetStack_SetIntrinsicChangeOfStateAlgorithmEnum; each call adds one occupancy state to Alarm_Values.
Related object types
Section titled “Related object types”Access Point, Access Door, Access Credential
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.32 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Description | CharacterString | O | no | no | "" |
| Global_Identifier | Unsigned32 | W | yes | yes | 0 |
| Occupancy_State | BACnetAccessZoneOccupancyState | R | yes | no | 0 |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | R | yes | no | 0 |
| Reliability | BACnetReliability | R1 | yes | no (yes while Out_Of_Service is true) | 0 |
| Out_Of_Service | Boolean | R | yes | no | false |
| Occupancy_Count | Unsigned | O1,3,4 | yes | no (yes while Out_Of_Service is true) | 0 |
| Occupancy_Count_Enable | Boolean | O3,4 | yes | no | false |
| Adjust_Value | Integer | O3,4,5 | yes | yes | 0 |
| Occupancy_Upper_Limit | Unsigned | O | no | no | 0 |
| Occupancy_Lower_Limit | Unsigned | O | no | no | 0 |
| Credentials_In_Zone | BACnetLIST of BACnetDeviceObjectReference | O | no | no | No default: the read fails. |
| Last_Credential_Added | BACnetDeviceObjectReference | O | no | no | A reference to Access Credential instance 4194303 (none). |
| Last_Credential_Added_Time | BACnetDateTime | O | no | no | No default: the read fails. |
| Last_Credential_Removed | BACnetDeviceObjectReference | O | no | no | A reference to Access Credential instance 4194303 (none). |
| Last_Credential_Removed_Time | BACnetDateTime | O | no | no | No default: the read fails. |
| Passback_Mode | BACnetAccessPassbackMode | O | no | no | 0 |
| Passback_Timeout | Unsigned | O2 | no | no | 0 |
| Entry_Points | BACnetLIST of BACnetDeviceObjectReference | R | yes | no | No default: the read fails. |
| Exit_Points | BACnetLIST of BACnetDeviceObjectReference | R | yes | no | No default: the read fails. |
| Time_Delay | Unsigned | O3,7 | no | no | 0 |
| Notification_Class | Unsigned | O3,7 | no | no | 0 |
| Alarm_Values | BACnetLIST of BACnetAccessZoneOccupancyState | O3,7 | no | no | 0 |
| Event_Enable | BACnetEventTransitionBits | O3,7 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O3,7 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O3,7 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O3,7 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O7 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O7 | no | no | "" |
| Event_Detection_Enable | Boolean | O3,7 | no | no | false |
| Event_Algorithm_Inhibit_Ref | BACnetObjectPropertyReference | O7 | no | no | No default: the read fails. |
| Event_Algorithm_Inhibit | Boolean | O7,8 | no | no | false |
| Time_Delay_Normal | Unsigned | O7 | no | no | 0 |
| Reliability_Evaluation_Inhibit | Boolean | O | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Audit_Level | BACnetAuditLevel | O9 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O9 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |