BACnetStack_SetBACnetSCSettings

bool BACnetStack_SetBACnetSCSettings(
const uint16_t maximumBVLCLength,
const uint16_t maximumNPDULength,
const uint16_t connectTimeout,
const uint16_t wsConnectTimeout,
const uint16_t wsReconnectTimeout,
const uint16_t heartbeatTimeout);

Sets the BACnet/SC transport-level timing and size settings shared by every SC connection this device makes.

Parameter Direction Description
maximumBVLCLength in The maximum BVLC message length this device accepts. With the current limits, a value below 1600 (the stack’s configuration floor) is refused, and a value above 6144 (the size of the buffer every BACnet/SC frame is received into) is saturated: the stack stores 6144, logs that it did, and the call still succeeds.
maximumNPDULength in The maximum NPDU length this device accepts. A value below 1497 or above 61327 is refused. With the current limits, a value above 6128 (the largest NPDU a frame received into the 6144-octet buffer can carry behind the 16-octet BVLC header of a frame relayed by a hub, without header options) is saturated: the stack stores 6128, logs that it did, and the call still succeeds. The Network Port’s Max_NPDU_Length_Accepted then reads 6128. The two lengths must agree: after saturation, maximumNPDULength + 16 (the BVLC header a hub adds to a relayed broadcast) must not exceed maximumBVLCLength, or the call is refused and nothing is changed. A peer that sized an NPDU to the advertised maximum would otherwise send a frame larger than the advertised BVLC maximum, which is discarded. A WriteProperty of Max_BVLC_Length_Accepted or Max_NPDU_Length_Accepted that would break the same rule is refused with Error(PROPERTY, VALUE_OUT_OF_RANGE).
connectTimeout in The connect wait timeout of 135-2024 AB.6.2, in seconds: how long the hub connector and the direct-connect initiator wait for a Connect-Accept after sending a Connect-Request, and how long the hub function waits for a Connect-Request on an accepted connection after its first frame. Also served as the Network Port’s SC_Connect_Wait_Timeout. It is not a TCP connect timeout; the hub connector’s WebSocket connect is timed by wsConnectTimeout instead. 5 to 300; a value outside that range is refused.
wsConnectTimeout in The WebSocket connect timeout in seconds.
wsReconnectTimeout in The WebSocket reconnect delay in seconds after a lost connection.
heartbeatTimeout in The WebSocket heartbeat timeout in seconds.

True if successfully set, otherwise false. All six values, and the agreement of the two lengths, are checked before any is applied, so a refused call leaves every setting unchanged. A later failure to apply the settings to one Network Port can still return false after earlier ports were updated.

Topic: BACnet/SC. Declared in CASBACnetStackDLL.h.