Skip to content
Version 6.1.0
Contact Us

Binary Input

A Binary Input object models a two-state input, such as a contact, a switch or a status signal. Its value is ACTIVE or INACTIVE. A Polarity setting lets the object invert the raw signal so the logical state is correct.

  • A fan run status contact
  • A door position switch
  • A filter differential pressure switch
  • A pump proof-of-flow signal
Property What it holds
Present_Value The current state, ACTIVE or INACTIVE.
Polarity Says whether the physical signal is normal or reversed relative to the logical state.
Active_Text A label for the active state, such as ‘Running’. Inactive_Text is the other label.
Alarm_Value The state that counts as an alarm.
Elapsed_Active_Time How long the input has been active in total, for runtime tracking.

Present_Value is not commandable. The standard pairs the type with the CHANGE_OF_STATE algorithm for intrinsic reporting, using Alarm_Value. Subscribers receive a change-of-value notification whenever the state changes.

Enable it with the STACK_OPTION_OBJECT_TYPE_BINARY_INPUT build option and add each object with BACnetStack_AddObject. Present_Value is enumerated, so the stack reads it through the callback you register with BACnetStack_RegisterCallbackGetPropertyEnumerated. Arm alarms with BACnetStack_SetIntrinsicChangeOfStateAlgorithmBool (an alarm value of true means active) after BACnetStack_SetAlarmsAndEventsForObjectEnabled.

Binary Output, Binary Value, Multi-state Input

The properties ASHRAE 135-2024 clause 12.6 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Present_Value BACnetBinaryPV R1 yes no (yes while Out_Of_Service is true) No default: value-not-initialized.
Description CharacterString O no no ""
Device_Type CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Event_State BACnetEventState R yes no 0
Reliability BACnetReliability O no no (yes while Out_Of_Service is true) 0
Out_Of_Service Boolean R yes no false
Polarity BACnetPolarity R yes no 0
Inactive_Text CharacterString O2 no no ""
Active_Text CharacterString O2 no no ""
Change_Of_State_Time BACnetDateTime O3 no no No default: the read fails.
Change_Of_State_Count Unsigned O3 no no 0
Time_Of_State_Count_Reset BACnetDateTime O3 no no No default: the read fails.
Elapsed_Active_Time Unsigned32 O4 no no 0
Time_Of_Active_Time_Reset BACnetDateTime O4 no no No default: the read fails.
Time_Delay Unsigned O5,7 no no 0
Notification_Class Unsigned O5,7 no no 0
Alarm_Value BACnetBinaryPV O5,7 no no 0
Event_Enable BACnetEventTransitionBits O5,7 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O5,7 no no An empty bit string.
Notify_Type BACnetNotifyType O5,7 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O5,7 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O7 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O7 no no ""
Event_Detection_Enable Boolean O5,7 no no false
Event_Algorithm_Inhibit_Ref BACnetObjectPropertyReference O7 no no No default: the read fails.
Event_Algorithm_Inhibit Boolean O7,8 no no false
Time_Delay_Normal Unsigned O7 no no 0
Reliability_Evaluation_Inhibit Boolean O9 no no false
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Interface_Value BACnetOptionalBinaryPV O no no Null
Audit_Level BACnetAuditLevel O10 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O10 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""