Analog Output

An Analog Output object models a controlled analog signal sent to equipment, such as a valve position or a fan speed. A client writes the value at a priority, and the device drives the output. Several writers can share the output, with the highest priority winning.

  • A chilled water valve position in percent
  • A variable frequency drive speed command
  • A damper actuator position
  • A dimmer level sent to an analog lighting driver
Property What it holds
Present_Value The value the output is driving, a real number. It is the result of the priority array.
Priority_Array Sixteen slots, one for each write priority. The lowest-numbered occupied slot wins.
Relinquish_Default The value used when every slot in the priority array is empty.
Units The engineering unit of the output.
COV_Increment The smallest change that triggers a change-of-value notification.

Present_Value is commandable. A client writes at a priority and later writes NULL to give that priority up. The standard pairs the type with the OUT_OF_RANGE algorithm for intrinsic reporting.

Enable it with the STACK_OPTION_OBJECT_TYPE_ANALOG_OUTPUT build option and add each object with BACnetStack_AddObject. The stack always treats it as commandable. It reads the priority array through the callback you register with BACnetStack_RegisterCallbackGetPropertyBool (is the slot empty) and the BACnetStack_RegisterCallbackGetPropertyReal callback (the slot value), and writes through the BACnetStack_RegisterCallbackSetPropertyReal callback. It never calls the plain Present_Value getter. Arm alarms with BACnetStack_SetIntrinsicOutOfRangeAlgorithm.

Analog Input, Analog Value, Binary Output

The properties ASHRAE 135-2024 clause 12.3 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Present_Value Real W yes yes Built by the stack from the priority array your callbacks serve, or Relinquish_Default when every slot is empty.
Description CharacterString O no no ""
Device_Type CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Event_State BACnetEventState R yes no 0
Reliability BACnetReliability O no no 0
Out_Of_Service Boolean R yes no false
Units BACnetEngineeringUnits R yes no 95 (no units)
Min_Pres_Value Real O no no 0.0
Max_Pres_Value Real O no no 0.0
Resolution Real O no no 0.0
Priority_Array BACnetARRAY[16] of BACnetOptionalReal R yes no Built by the stack from your callbacks.
Relinquish_Default Real R yes no No default: value-not-initialized until a callback or a client write supplies one.
COV_Increment Real O1 no no 0.0
Time_Delay Unsigned O2,4 no no 0
Notification_Class Unsigned O2,4 no no 0
High_Limit Real O2,4 no no 0.0
Low_Limit Real O2,4 no no 0.0
Deadband Real O2,4 no no 0.0
Limit_Enable BACnetLimitEnable O2,4 no no An empty bit string.
Event_Enable BACnetEventTransitionBits O2,4 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O2,4 no no An empty bit string.
Notify_Type BACnetNotifyType O2,4 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O2,4 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O4 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O4 no no ""
Event_Detection_Enable Boolean O2,4 no no false
Event_Algorithm_Inhibit_Ref BACnetObjectPropertyReference O4 no no No default: the read fails.
Event_Algorithm_Inhibit Boolean O4,5 no no false
Time_Delay_Normal Unsigned O4 no no 0
Reliability_Evaluation_Inhibit Boolean O6 no no false
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Interface_Value BACnetOptionalReal O no no Null
Current_Command_Priority BACnetOptionalUnsigned R yes no Built by the stack from your callbacks.
Value_Source BACnetValueSource O7,9,11 no no No default: the read fails.
Value_Source_Array BACnetARRAY[16] of BACnetValueSource O8,10 no no No default: the read fails.
Last_Command_Time BACnetTimeStamp O8,10 no no No default: the read fails.
Command_Time_Array BACnetARRAY[16] of BACnetTimeStamp O10 no no No default: the read fails.
Audit_Level BACnetAuditLevel O12 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O12 not in profile not in profile No default: the read fails.
Audit_Priority_Filter BACnetOptionalPriorityFilter O12 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""