Binary Value

A Binary Value is a two-state value that does not map to a physical input or output. It holds a flag, mode or status that lives in software. A device uses it for things like an occupancy override, an enable switch or a fault summary.

  • An occupied/unoccupied mode flag
  • A software enable for a control loop
  • A summary alarm flag
  • A manual override switch
  • A schedule output that other devices read
Property What it holds
Present_Value The current state, ACTIVE or INACTIVE. Writable if the object is commandable or the host allows it.
Active_Text Optional label shown for the ACTIVE state, such as Occupied.
Inactive_Text Optional label shown for the INACTIVE state, such as Unoccupied.
Priority_Array Present only when the object is commandable. Holds one command per priority from 1 to 16.
Relinquish_Default Present only when the object is commandable. The value used when every priority slot is empty.
Alarm_Value With intrinsic reporting, the state that puts the object into OFFNORMAL.

A Binary Value may be commandable or not. With intrinsic reporting, the standard pairs it with the CHANGE_OF_STATE algorithm: the object goes OFFNORMAL when Present_Value equals the alarm value for the time delay. Clients can subscribe to changes of Present_Value and Status_Flags.

Enable it with the STACK_OPTION_OBJECT_TYPE_BINARY_VALUE build option and add each object with BACnetStack_AddObject. Present_Value is served through the callback you register with BACnetStack_RegisterCallbackGetPropertyEnumerated and the BACnetStack_RegisterCallbackSetPropertyEnumerated callback. The object becomes commandable once you enable both PriorityArray and RelinquishDefault; the stack then reads the priority array through the BACnetStack_RegisterCallbackGetPropertyBool callback and the BACnetStack_RegisterCallbackGetPropertyEnumerated callback instead of the plain Present_Value read. Arm the alarm with BACnetStack_SetIntrinsicChangeOfStateAlgorithmBool (an alarm value of true means active), after BACnetStack_SetAlarmsAndEventsForObjectEnabled.

Binary Input, Binary Output, Multi-state Value, Analog Value

The properties ASHRAE 135-2024 clause 12.8 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Present_Value BACnetBinaryPV R1 yes no (yes while Out_Of_Service is true) No default: value-not-initialized. Once Priority_Array and Relinquish_Default are enabled, built by the stack from the priority array your callbacks serve.
Description CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Event_State BACnetEventState R yes no 0
Reliability BACnetReliability O no no (yes while Out_Of_Service is true) 0
Out_Of_Service Boolean R yes no false
Inactive_Text CharacterString O2 no no ""
Active_Text CharacterString O2 no no ""
Change_Of_State_Time BACnetDateTime O3 no no No default: the read fails.
Change_Of_State_Count Unsigned O3 no no 0
Time_Of_State_Count_Reset BACnetDateTime O3 no no No default: the read fails.
Elapsed_Active_Time Unsigned32 O4 no no 0
Time_Of_Active_Time_Reset BACnetDateTime O4 no no No default: the read fails.
Minimum_Off_Time Unsigned32 O no no 0
Minimum_On_Time Unsigned32 O no no 0
Priority_Array BACnetARRAY[16] of BACnetOptionalBinaryPV O5 no no Built by the stack from your callbacks.
Relinquish_Default BACnetBinaryPV O5 no no No default: value-not-initialized until a callback or a client write supplies one.
Time_Delay Unsigned O6,8 no no 0
Notification_Class Unsigned O6,8 no no 0
Alarm_Value BACnetBinaryPV O6,8 no no 0
Event_Enable BACnetEventTransitionBits O6,8 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O6,8 no no An empty bit string.
Notify_Type BACnetNotifyType O6,8 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O6,8 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O8 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O8 no no ""
Event_Detection_Enable Boolean O6,8 no no false
Event_Algorithm_Inhibit_Ref BACnetObjectPropertyReference O8 no no No default: the read fails.
Event_Algorithm_Inhibit Boolean O8,9 no no false
Time_Delay_Normal Unsigned O8 no no 0
Reliability_Evaluation_Inhibit Boolean O10 no no false
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Current_Command_Priority BACnetOptionalUnsigned O5 no no Built by the stack from your callbacks.
Value_Source BACnetValueSource O11,13,15 no no No default: the read fails.
Value_Source_Array BACnetARRAY[16] of BACnetValueSource O12,14 no no No default: the read fails.
Last_Command_Time BACnetTimeStamp O12,14 no no No default: the read fails.
Command_Time_Array BACnetARRAY[16] of BACnetTimeStamp O14 no no No default: the read fails.
Audit_Level BACnetAuditLevel O16 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O16 not in profile not in profile No default: the read fails.
Audit_Priority_Filter BACnetOptionalPriorityFilter O17 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""