DateTime Pattern Value
A DateTime Pattern Value holds a date and a time in which some fields may be wildcards. It matches many moments at once, such as 06:00 on any weekday. A device exposes one when a client needs to read or set a recurring moment.
Typical uses
Section titled “Typical uses”- Every weekday at 06:00
- The first of each month at midnight
- Any day at noon
- A recurring report time
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Present_Value | A date and time in which any field can be a wildcard (unspecified). |
| Priority_Array | Present only when the object is commandable. |
| Relinquish_Default | Present only when the object is commandable. Used when no priority slot holds a value. |
How it behaves
Section titled “How it behaves”The standard defines no event algorithm for this type. With intrinsic reporting it reports faults only. Clients can subscribe to changes of Present_Value and Status_Flags.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_DATE_TIME_PATTERN_VALUE build option and add each object with BACnetStack_AddObject. Present_Value is read through the callback you register with BACnetStack_RegisterCallbackGetPropertyDate and the BACnetStack_RegisterCallbackGetPropertyTime callback together. The object becomes commandable once you enable both PriorityArray and RelinquishDefault. The standard applies no event algorithm to this type and the stack serves no event state for it, so there is nothing to arm: BACnetStack_SetAlarmsAndEventsForObjectEnabled accepts the object but changes nothing a client can see.
Related object types
Section titled “Related object types”DateTime Value, Date Pattern Value, Time Pattern Value, Schedule
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.46 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Description | CharacterString | O | no | no | "" |
| Present_Value | BACnetDateTimePattern | R1 | yes | no (yes while Out_Of_Service is true) | No default: value-not-initialized. Once Priority_Array and Relinquish_Default are enabled, built by the stack from the priority array your callbacks serve. |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | O | no | no | 0 |
| Reliability | BACnetReliability | O | no | no (yes while Out_Of_Service is true) | 0 |
| Out_Of_Service | Boolean | O | no | no | false |
| Is_UTC | Boolean | O | no | no | false |
| Priority_Array | BACnetARRAY[16] of BACnetOptionalDateTimePattern | O2 | no | no | Built by the stack from your callbacks. |
| Relinquish_Default | BACnetDateTime | O2 | no | no | No default: value-not-initialized until a callback or a client write supplies one. |
| Reliability_Evaluation_Inhibit | Boolean | O3 | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Event_Detection_Enable | Boolean | O4,5 | no | no | false |
| Notification_Class | Unsigned | O4,5 | no | no | 0 |
| Event_Enable | BACnetEventTransitionBits | O4,5 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O4,5 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O4,5 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O4,5 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O5 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O5 | no | no | "" |
| Current_Command_Priority | BACnetOptionalUnsigned | O2 | no | no | Built by the stack from your callbacks. |
| Value_Source | BACnetValueSource | O6,8,10 | no | no | No default: the read fails. |
| Value_Source_Array | BACnetARRAY[16] of BACnetValueSource | O7,9 | no | no | No default: the read fails. |
| Last_Command_Time | BACnetTimeStamp | O7,9 | no | no | No default: the read fails. |
| Command_Time_Array | BACnetARRAY[16] of BACnetTimeStamp | O9 | no | no | No default: the read fails. |
| Audit_Level | BACnetAuditLevel | O11 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O11 | not in profile | not in profile | No default: the read fails. |
| Audit_Priority_Filter | BACnetOptionalPriorityFilter | O11 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |