Loop
A Loop object represents a control loop, usually PID, in a controller. It exposes the loop’s output, the controlled variable, the setpoint and the tuning gains, so a client can watch and tune the loop. A controller exposes one per loop that operators need to see.
Typical uses
Section titled “Typical uses”- Tune the gains of a temperature control loop
- Show setpoint, process value and output on one screen
- Alarm when the process drifts from the setpoint
- Switch a loop between automatic and manual
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Present_Value | The loop’s current output. |
| Controlled_Variable_Value | The measured value the loop is controlling. |
| Setpoint | The target for the controlled variable. |
| Proportional_Constant | The proportional gain. Integral and derivative gains have their own properties. |
| Manipulated_Variable_Reference | The property the loop writes its output to. |
| Action | Whether the loop acts directly or in reverse. |
How it behaves
Section titled “How it behaves”The loop algorithm itself is a local matter in the device. The standard pairs the Loop with the FLOATING_LIMIT algorithm, which alarms when the controlled variable drifts too far from the setpoint. It sends change-of-value notices when Present_Value moves by COV_Increment.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_LOOP build option and add each object with BACnetStack_AddObject. Serve Present_Value with the callback you register with BACnetStack_RegisterCallbackGetPropertyReal and accept writes with the BACnetStack_RegisterCallbackSetPropertyReal callback; Object_Name uses the BACnetStack_RegisterCallbackGetPropertyCharacterString callback. The stack does not run the PID algorithm; your application does. Arm the drift alarm with BACnetStack_SetAlarmsAndEventsForObjectEnabled and then BACnetStack_SetIntrinsicFloatingLimitAlgorithm, which takes the setpoint and separate low and high difference limits.
Related object types
Section titled “Related object types”Analog Input, Analog Output, Analog Value
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.17 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Present_Value | Real | R7 | yes | no (yes while Out_Of_Service is true) | No default: value-not-initialized. |
| Description | CharacterString | O | no | no | "" |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | R | yes | no | 0 |
| Reliability | BACnetReliability | O7 | no | no (yes while Out_Of_Service is true) | 0 |
| Out_Of_Service | Boolean | R | yes | no | false |
| Update_Interval | Unsigned | O | no | no | 0 |
| Output_Units | BACnetEngineeringUnits | R | yes | no | 0 |
| Manipulated_Variable_Reference | BACnetObjectPropertyReference | R | yes | no | No default: the read fails. |
| Controlled_Variable_Reference | BACnetObjectPropertyReference | R | yes | no | No default: the read fails. |
| Controlled_Variable_Value | Real | R | yes | no | 0.0 |
| Controlled_Variable_Units | BACnetEngineeringUnits | R | yes | no | 0 |
| Setpoint_Reference | BACnetSetpointReference | R | yes | no | No default: the read fails. |
| Setpoint | Real | R | yes | no | 0.0 |
| Action | BACnetAction | R | yes | no | 0 |
| Proportional_Constant | Real | O1 | no | no | 0.0 |
| Proportional_Constant_Units | BACnetEngineeringUnits | O1 | no | no | 0 |
| Integral_Constant | Real | O2 | no | no | 0.0 |
| Integral_Constant_Units | BACnetEngineeringUnits | O2 | no | no | 0 |
| Derivative_Constant | Real | O3 | no | no | 0.0 |
| Derivative_Constant_Units | BACnetEngineeringUnits | O3 | no | no | 0 |
| Bias | Real | O | no | no | 0.0 |
| Maximum_Output | Real | O | no | no | 0.0 |
| Minimum_Output | Real | O | no | no | 0.0 |
| Priority_For_Writing | Unsigned(1..16) | R | yes | no | 0 |
| COV_Increment | Real | O4 | no | no | 0.0 |
| Time_Delay | Unsigned | O5,8 | no | no | 0 |
| Notification_Class | Unsigned | O5,8 | no | no | 0 |
| Error_Limit | Real | O5,8 | no | no | 0.0 |
| Deadband | Real | O5,8 | no | no | 0.0 |
| Event_Enable | BACnetEventTransitionBits | O5,8 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O5,8 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O5,8 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O5,8 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O8 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O8 | no | no | "" |
| Event_Detection_Enable | Boolean | O5,8 | no | no | false |
| Event_Algorithm_Inhibit_Ref | BACnetObjectPropertyReference | O8 | no | no | No default: the read fails. |
| Event_Algorithm_Inhibit | Boolean | O8,9 | no | no | false |
| Time_Delay_Normal | Unsigned | O8 | no | no | 0 |
| Reliability_Evaluation_Inhibit | Boolean | O10 | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Low_Diff_Limit | BACnetOptionalReal | O | no | no | No default: the read fails. |
| Audit_Level | BACnetAuditLevel | O11 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O11 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |