Multi-state Value

A Multi-state Value object holds one numbered state that the device keeps for its own purposes, such as an operating mode or a status code. It is not tied to a physical input or output. The object reports how many states exist and can label each one.

  • Building mode: Occupied, Unoccupied, Standby
  • Setpoint profile selector
  • Equipment status code with named states
  • Season selector: Heating, Cooling, Auto
  • Alarm priority level
Property What it holds
Present_Value The current state, a number from 1 to Number_Of_States.
Number_Of_States How many states the value can take.
State_Text An optional array of labels, one per state.
Alarm_Values The states that count as an alarm, when the object reports intrinsic events.
Priority_Array Optional. Present only when the value is made commandable; sixteen slots, one per priority.
Relinquish_Default Optional. The state used when every priority slot is empty.

Without a priority array, a client can write the value only if the device allows it; with one, the value is commandable. When it reports intrinsic events, the standard pairs it with the CHANGE_OF_STATE algorithm: the object goes off-normal when Present_Value enters one of the Alarm_Values and returns to normal when it leaves them. COV notifications go out on any change to Present_Value or Status_Flags.

Enable it with the STACK_OPTION_OBJECT_TYPE_MULTISTATE_VALUE build option and add each object with BACnetStack_AddObject. Serve Present_Value with the callback you register with BACnetStack_RegisterCallbackGetPropertyUnsignedInteger and, if clients may write it, the BACnetStack_RegisterCallbackSetPropertyUnsignedInteger callback. The object becomes commandable once you enable both PriorityArray and RelinquishDefault; from then on the stack reads the priority array through the callbacks instead of the plain getter. To arm alarms, enable alarms for the object and call BACnetStack_SetIntrinsicChangeOfStateAlgorithmUnsigned once for each alarm state. Call BACnetStack_UpdateValue whenever the value you serve changes, so COV, trend logs and alarms see it.

Multi-state Input, Multi-state Output, Integer Value

The properties ASHRAE 135-2024 clause 12.20 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Present_Value Unsigned R1 yes no (yes while Out_Of_Service is true) No default: value-not-initialized. Once Priority_Array and Relinquish_Default are enabled, built by the stack from the priority array your callbacks serve.
Description CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Event_State BACnetEventState R yes no 0
Reliability BACnetReliability O no no (yes while Out_Of_Service is true) 0
Out_Of_Service Boolean R yes no false
Number_Of_States Unsigned R yes no No default: value-not-initialized until a callback or a client write supplies one.
State_Text BACnetARRAY[N] of CharacterString O no no ""
Priority_Array BACnetARRAY[16] of BACnetOptionalUnsigned O3 no no Built by the stack from your callbacks.
Relinquish_Default Unsigned O3 no no No default: value-not-initialized until a callback or a client write supplies one.
Time_Delay Unsigned O4,6 no no 0
Notification_Class Unsigned O4,6 no no 0
Alarm_Values BACnetLIST of Unsigned O4,6 no no 0
Fault_Values BACnetLIST of Unsigned O8 no no 0
Event_Enable BACnetEventTransitionBits O4,6 no no An empty bit string.
Acked_Transitions BACnetEventTransitionBits O4,6 no no An empty bit string.
Notify_Type BACnetNotifyType O4,6 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O4,6 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O6 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O6 no no ""
Event_Detection_Enable Boolean O4,6 no no false
Event_Algorithm_Inhibit_Ref BACnetObjectPropertyReference O6 no no No default: the read fails.
Event_Algorithm_Inhibit Boolean O6,7 no no false
Time_Delay_Normal Unsigned O6 no no 0
Reliability_Evaluation_Inhibit Boolean O8 no no false
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Current_Command_Priority BACnetOptionalUnsigned O3 no no Built by the stack from your callbacks.
Value_Source BACnetValueSource O9,11,13 no no No default: the read fails.
Value_Source_Array BACnetARRAY[16] of BACnetValueSource O10,12 no no No default: the read fails.
Last_Command_Time BACnetTimeStamp O10,12 no no No default: the read fails.
Command_Time_Array BACnetARRAY[16] of BACnetTimeStamp O12 no no No default: the read fails.
Audit_Level BACnetAuditLevel O14 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O14 not in profile not in profile No default: the read fails.
Audit_Priority_Filter BACnetOptionalPriorityFilter O15 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""