OctetString Value
An OctetString Value object holds a string of raw bytes under a name. Use it for data that is not text and not a number, such as a binary key, a hardware address or a block of packed data. Clients read it, and may write it if the device allows.
Typical uses
Section titled “Typical uses”- MAC or hardware address of an attached device
- Firmware or configuration checksum
- Opaque identifier read from a card or tag
- Packed status bytes from equipment
- Binary key or token a client may write
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Present_Value | The bytes the object holds. A client reads them as a byte string of any length the device supports. |
| Priority_Array | Optional. Present only when the value is commandable; sixteen priority slots. |
| Relinquish_Default | Optional. The value used when every priority slot is empty. |
| Out_Of_Service | When true, Present_Value stops following the real source and a client can write it for testing. |
How it behaves
Section titled “How it behaves”The object is not commandable unless you give it a priority array. It has no event algorithm and no intrinsic reporting. COV notifications go out on any change to Present_Value or Status_Flags.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_OCTET_STRING_VALUE build option and add each object with BACnetStack_AddObject. Serve Present_Value with the callback you register with BACnetStack_RegisterCallbackGetPropertyOctetString and, if clients may write it, the BACnetStack_RegisterCallbackSetPropertyOctetString callback. The object becomes commandable once you enable both PriorityArray and RelinquishDefault. Alarms are not available for this type: BACnetStack_SetAlarmsAndEventsForObjectEnabled returns false for it. Call BACnetStack_UpdateValue whenever the value you serve changes, so COV, trend logs and alarms see it.
Related object types
Section titled “Related object types”CharacterString Value, BitString Value, Integer Value
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.41 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Description | CharacterString | O | no | no | "" |
| Present_Value | OctetString | R1 | yes | no (yes while Out_Of_Service is true) | No default: value-not-initialized. Once Priority_Array and Relinquish_Default are enabled, built by the stack from the priority array your callbacks serve. |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | O | no | no | 0 |
| Reliability | BACnetReliability | O | no | no (yes while Out_Of_Service is true) | 0 |
| Out_Of_Service | Boolean | O | no | no | false |
| Priority_Array | BACnetARRAY[16] of BACnetOptionalOctetString | O2 | no | no | Built by the stack from your callbacks. |
| Relinquish_Default | OctetString | O2 | no | no | No default: value-not-initialized until a callback or a client write supplies one. |
| Reliability_Evaluation_Inhibit | Boolean | O3 | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Current_Command_Priority | BACnetOptionalUnsigned | O2 | no | no | Built by the stack from your callbacks. |
| Value_Source | BACnetValueSource | O4,6,8 | no | no | No default: the read fails. |
| Value_Source_Array | BACnetARRAY[16] of BACnetValueSource | O5,7 | no | no | No default: the read fails. |
| Last_Command_Time | BACnetTimeStamp | O5,7 | no | no | No default: the read fails. |
| Command_Time_Array | BACnetARRAY[16] of BACnetTimeStamp | O7 | no | no | No default: the read fails. |
| Audit_Level | BACnetAuditLevel | O9 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O9 | not in profile | not in profile | No default: the read fails. |
| Audit_Priority_Filter | BACnetOptionalPriorityFilter | O9 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |