Positive Integer Value
A Positive Integer Value object holds a whole number that is zero or greater, with engineering units. Use it for counts, ratings and other values that are never negative and can be larger than a small state number. Clients read it and, if the device allows, write it.
Typical uses
Section titled “Typical uses”- Run-time hours of equipment
- Number of occupants in a room
- Target speed in rpm
- Event or start counter
- Rated capacity of a unit
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Present_Value | The unsigned whole number the object holds. |
| Units | The engineering units of the value. |
| COV_Increment | How far Present_Value must move before a subscribed client is notified. Present only when the object supports COV. |
| Priority_Array | Optional. Present only when the value is commandable; sixteen priority slots. |
| Low_Limit / High_Limit | Optional limits for alarms. The object reports off-normal when the value passes one, after the time delay. |
How it behaves
Section titled “How it behaves”The object is commandable only if you give it a priority array. When it reports intrinsic events, the standard pairs it with the UNSIGNED_OUT_OF_RANGE algorithm, which has a deadband for the return to normal. COV notifications go out when Present_Value changes by COV_Increment or on any change to Status_Flags.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_POSITIVE_INTEGER_VALUE build option and add each object with BACnetStack_AddObject. Serve Present_Value with the callback you register with BACnetStack_RegisterCallbackGetPropertyUnsignedInteger and, if clients may write it, the BACnetStack_RegisterCallbackSetPropertyUnsignedInteger callback. The object becomes commandable once you enable both PriorityArray and RelinquishDefault. To arm alarms, enable alarms for the object and call BACnetStack_SetIntrinsicUnsignedOutOfRangeAlgorithm; do not use BACnetStack_SetIntrinsicUnsignedRangeAlgorithm, which is the no-deadband variant meant for other types. Call BACnetStack_UpdateValue whenever the value you serve changes, so COV, trend logs and alarms see it. The stack has no fault out-of-range setter for this type: BACnetStack_SetFaultOutOfRangeAlgorithmReal refuses it.
Related object types
Section titled “Related object types”Integer Value, Analog Value, Accumulator
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.44 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Description | CharacterString | O | no | no | "" |
| Present_Value | Unsigned | R1 | yes | no (yes while Out_Of_Service is true) | No default: value-not-initialized. Once Priority_Array and Relinquish_Default are enabled, built by the stack from the priority array your callbacks serve. |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | O4 | no | no | 0 |
| Reliability | BACnetReliability | O | no | no (yes while Out_Of_Service is true) | 0 |
| Out_Of_Service | Boolean | O | no | no | false |
| Units | BACnetEngineeringUnits | R | yes | no | 95 (no units) |
| Priority_Array | BACnetARRAY[16] of BACnetOptionalUnsigned | O2 | no | no | Built by the stack from your callbacks. |
| Relinquish_Default | Unsigned | O2 | no | no | No default: value-not-initialized until a callback or a client write supplies one. |
| COV_Increment | Unsigned | O3 | no | no | 0 |
| Time_Delay | Unsigned | O4,6 | no | no | 0 |
| Notification_Class | Unsigned | O4,6 | no | no | 0 |
| High_Limit | Unsigned | O4,6 | no | no | 0 |
| Low_Limit | Unsigned | O4,6 | no | no | 0 |
| Deadband | Unsigned | O4,6 | no | no | 0 |
| Limit_Enable | BACnetLimitEnable | O4,6 | no | no | An empty bit string. |
| Event_Enable | BACnetEventTransitionBits | O4,6 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O4,6 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O4,6 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O4,6 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O6 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O6 | no | no | "" |
| Event_Detection_Enable | Boolean | O4,6 | no | no | false |
| Event_Algorithm_Inhibit_Ref | BACnetObjectPropertyReference | O6 | no | no | No default: the read fails. |
| Event_Algorithm_Inhibit | Boolean | O6,7 | no | no | false |
| Time_Delay_Normal | Unsigned | O6 | no | no | 0 |
| Reliability_Evaluation_Inhibit | Boolean | O8 | no | no | false |
| Min_Pres_Value | Unsigned | O | no | no | 0 |
| Max_Pres_Value | Unsigned | O | no | no | 0 |
| Resolution | Unsigned | O | no | no | 0 |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Fault_High_Limit | Unsigned | O9 | no | no | 0 |
| Fault_Low_Limit | Unsigned | O9 | no | no | 0 |
| Current_Command_Priority | BACnetOptionalUnsigned | O2 | no | no | Built by the stack from your callbacks. |
| Value_Source | BACnetValueSource | O10,12,14 | no | no | No default: the read fails. |
| Value_Source_Array | BACnetARRAY[16] of BACnetValueSource | O11,13 | no | no | No default: the read fails. |
| Last_Command_Time | BACnetTimeStamp | O11,13 | no | no | No default: the read fails. |
| Command_Time_Array | BACnetARRAY[16] of BACnetTimeStamp | O13 | no | no | No default: the read fails. |
| Audit_Level | BACnetAuditLevel | O15 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O15 | not in profile | not in profile | No default: the read fails. |
| Audit_Priority_Filter | BACnetOptionalPriorityFilter | O15 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |