A Program object gives a network view of an application program running in the device. A client can see whether the program is running, halted or idle, and can ask it to load, run, halt, restart or unload. What the program actually does stays private to the device.

  • Control sequence a technician can start and stop remotely
  • Report why a program halted
  • Restart a stuck application from a workstation
  • Show which program file a device runs
  • Expose a vendor-specific application to tools
Property What it holds
Program_State The current state of the program, such as idle, loading, running, waiting, halted or unloading.
Program_Change Where a client requests a change: ready, load, run, halt, restart or unload. The program returns it to ready when it has acted.
Reason_For_Halt Why the program last stopped, for example normal, load failed or a program fault.
Description_Of_Halt Optional text giving more detail about the halt.
Program_Location Optional text naming where the program is held.

The object is not commandable and the standard applies no event algorithm to it. When it reports intrinsic faults, a reliability fault is shown through Event_State. Which changes a program accepts, and how it moves between states, is up to the program.

The customer interface has no function for this type and no callback for a change request. A client’s write to Program_Change reaches the callback you register with BACnetStack_RegisterCallbackSetPropertyEnumerated like any other enumerated write, and your application must act on it and update Program_State itself. The type is on in the full target. In the embedded target, define STACK_OPTION_OBJECT_TYPE_PROGRAM yourself (see Configuring a build). Create the object with BACnetStack_AddObject. The stack serves the object identifier, object type, property list and status flags itself; your callbacks serve every other property.

Device, Command

The properties ASHRAE 135-2024 clause 12.22 defines for this object type.

How to read the table:

  • Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
  • Present by default: yes means the stack presents the property as soon as you add the object; no means it is optional and you turn it on with BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code.
  • Writable is whether a client can write the property by default. Change it with BACnetStack_SetPropertyWritable.
  • not in profile means the stack does not offer this property for this object type.
  • Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
Property Datatype Conformance Present by default Writable Value when your callback does not answer
Object_Identifier BACnetObjectIdentifier R yes no Held by the stack.
Object_Name CharacterString R yes no "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1.
Object_Type BACnetObjectType R yes no Held by the stack.
Program_State BACnetProgramState R yes no 0
Program_Change BACnetProgramRequest W yes yes 0
Reason_For_Halt BACnetProgramError O1 no no 0
Description_Of_Halt CharacterString O1 no no ""
Program_Location CharacterString O no no ""
Description CharacterString O no no ""
Instance_Of CharacterString O no no ""
Status_Flags BACnetStatusFlags R yes no Built by the stack from your callbacks.
Reliability BACnetReliability O no no 0
Out_Of_Service Boolean R yes no false
Event_Detection_Enable Boolean O2,3 no no false
Notification_Class Unsigned O2,3 no no 0
Event_Enable BACnetEventTransitionBits O2,3 no no An empty bit string.
Event_State BACnetEventState O2,3 no no 0
Acked_Transitions BACnetEventTransitionBits O2,3 no no An empty bit string.
Notify_Type BACnetNotifyType O2,3 no no 0
Event_Time_Stamps BACnetARRAY[3] of BACnetTimeStamp O2,3 no no No default: the read fails.
Event_Message_Texts BACnetARRAY[3] of CharacterString O3 no no ""
Event_Message_Texts_Config BACnetARRAY[3] of CharacterString O3 no no ""
Reliability_Evaluation_Inhibit Boolean O4 no no false
Property_List BACnetARRAY[N] of BACnetPropertyIdentifier R yes no Held by the stack.
Audit_Level BACnetAuditLevel O5 not in profile not in profile No default: the read fails.
Auditable_Operations BACnetAuditOperationFlags O5 not in profile not in profile No default: the read fails.
Tags BACnetARRAY[N] of BACnetNameValue O no no No default: the read fails.
Profile_Location CharacterString O no no ""
Profile_Name CharacterString O no no ""