Program
A Program object gives a network view of an application program running in the device. A client can see whether the program is running, halted or idle, and can ask it to load, run, halt, restart or unload. What the program actually does stays private to the device.
Typical uses
Section titled “Typical uses”- Control sequence a technician can start and stop remotely
- Report why a program halted
- Restart a stuck application from a workstation
- Show which program file a device runs
- Expose a vendor-specific application to tools
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Program_State | The current state of the program, such as idle, loading, running, waiting, halted or unloading. |
| Program_Change | Where a client requests a change: ready, load, run, halt, restart or unload. The program returns it to ready when it has acted. |
| Reason_For_Halt | Why the program last stopped, for example normal, load failed or a program fault. |
| Description_Of_Halt | Optional text giving more detail about the halt. |
| Program_Location | Optional text naming where the program is held. |
How it behaves
Section titled “How it behaves”The object is not commandable and the standard applies no event algorithm to it. When it reports intrinsic faults, a reliability fault is shown through Event_State. Which changes a program accepts, and how it moves between states, is up to the program.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”The customer interface has no function for this type and no callback for a change request. A client’s write to Program_Change reaches the callback you register with BACnetStack_RegisterCallbackSetPropertyEnumerated like any other enumerated write, and your application must act on it and update Program_State itself. The type is on in the full target. In the embedded target, define STACK_OPTION_OBJECT_TYPE_PROGRAM yourself (see Configuring a build). Create the object with BACnetStack_AddObject. The stack serves the object identifier, object type, property list and status flags itself; your callbacks serve every other property.
Related object types
Section titled “Related object types”Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.22 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Program_State | BACnetProgramState | R | yes | no | 0 |
| Program_Change | BACnetProgramRequest | W | yes | yes | 0 |
| Reason_For_Halt | BACnetProgramError | O1 | no | no | 0 |
| Description_Of_Halt | CharacterString | O1 | no | no | "" |
| Program_Location | CharacterString | O | no | no | "" |
| Description | CharacterString | O | no | no | "" |
| Instance_Of | CharacterString | O | no | no | "" |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Reliability | BACnetReliability | O | no | no | 0 |
| Out_Of_Service | Boolean | R | yes | no | false |
| Event_Detection_Enable | Boolean | O2,3 | no | no | false |
| Notification_Class | Unsigned | O2,3 | no | no | 0 |
| Event_Enable | BACnetEventTransitionBits | O2,3 | no | no | An empty bit string. |
| Event_State | BACnetEventState | O2,3 | no | no | 0 |
| Acked_Transitions | BACnetEventTransitionBits | O2,3 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O2,3 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O2,3 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O3 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O3 | no | no | "" |
| Reliability_Evaluation_Inhibit | Boolean | O4 | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Audit_Level | BACnetAuditLevel | O5 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O5 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |