Staging
A Staging object turns one number into a pattern of on and off outputs. You define stages, each with a limit and a set of states for a group of binary objects. As the value rises and falls, the object moves between stages and writes the matching states to the binary objects it controls.
Typical uses
Section titled “Typical uses”- Stage chillers on as load rises
- Switch banks of lights by light level
- Bring boiler stages on and off with demand
- Stage fans or pumps by pressure
- Drive several relays from one setpoint
Key properties
Section titled “Key properties”| Property | What it holds |
|---|---|
| Present_Value | The number that selects the stage. A write is held between Min_Pres_Value and Max_Pres_Value. |
| Present_Stage | The index of the active stage. It is not available until the object has chosen a stage after a restart or a change of the stage table. |
| Stages | The stage table. Each stage has a limit, a deadband and the on or off state for every target. |
| Target_References | The Binary Output, Binary Value or Binary Lighting Output objects the stages control. |
| Priority_For_Writing | The priority used when writing to the targets. |
How it behaves
Section titled “How it behaves”The object has no priority array, and the standard applies no event algorithm to it. COV notifications go out when Present_Value changes by COV_Increment, when Present_Stage changes, or on any change to Status_Flags.
With the CAS BACnet Stack
Section titled “With the CAS BACnet Stack”Enable it with the STACK_OPTION_OBJECT_TYPE_STAGING build option. It is on in the full target; in the embedded target, define it yourself (see Configuring a build). CASBACnetStackDLL.h has no function dedicated to this type, so create it with BACnetStack_AddObject. The stack serves the object identifier, object type, property list and status flags itself; your callbacks serve every other property, matched to its datatype. Call BACnetStack_UpdateValue whenever the value you serve changes, so COV, trend logs and alarms see it.
Related object types
Section titled “Related object types”Binary Output, Binary Value, Binary Lighting Output
Properties
Section titled “Properties”The properties ASHRAE 135-2024 clause 12.62 defines for this object type.
How to read the table:
- Conformance is what the standard asks of every object of this type: R is required, W is required and writable by a client, O is optional. A digit after the letter marks a condition in the standard that decides when the property is present or writable, such as support for intrinsic reporting.
- Present by default: yes means the stack presents the property as soon as you add the object; no means it
is optional and you turn it on with
BACnetStack_SetPropertyEnabled. This is the stack’s starting setup, so it can differ from the conformance code. - Writable is whether a client can write the property by default. Change it with
BACnetStack_SetPropertyWritable. - not in profile means the stack does not offer this property for this object type.
- Value when your callback does not answer: “Held by the stack” means the stack stores and serves the value itself and does not ask your callbacks. Otherwise it is the value the stack answers when your callback declines or is not registered.
| Property | Datatype | Conformance | Present by default | Writable | Value when your callback does not answer |
|---|---|---|---|---|---|
| Object_Identifier | BACnetObjectIdentifier | R | yes | no | Held by the stack. |
| Object_Name | CharacterString | R | yes | no | "Object <type>,<instance>", such as "Object 0,1" for Analog Input 1. |
| Object_Type | BACnetObjectType | R | yes | no | Held by the stack. |
| Present_Value | Real | W | yes | yes | No default: value-not-initialized. |
| Present_Stage | Unsigned | R | yes | no | 0 |
| Stages | BACnetARRAY[N] of BACnetStageLimitValue | R1 | yes | no | No default: the read fails. |
| Stage_Names | BACnetARRAY[N] of CharacterString | O1 | no | no | "" |
| Status_Flags | BACnetStatusFlags | R | yes | no | Built by the stack from your callbacks. |
| Event_State | BACnetEventState | R | yes | no | 0 |
| Reliability | BACnetReliability | R | yes | no | 0 |
| Out_Of_Service | Boolean | R | yes | no | false |
| Description | CharacterString | O | no | no | "" |
| Units | BACnetEngineeringUnits | R | yes | no | 95 (no units) |
| Target_References | BACnetARRAY[N] of BACnetDeviceObjectReference | R2 | yes | no | No default: the read fails. |
| Priority_For_Writing | Unsigned(1..16) | R | yes | no | 0 |
| Default_Present_Value | Real | O | no | no | 0.0 |
| Min_Pres_Value | Real | R | yes | no | 0.0 |
| Max_Pres_Value | Real | R | yes | no | 0.0 |
| COV_Increment | Real | O3 | no | no | 0.0 |
| Notification_Class | Unsigned | O4,5 | no | no | 0 |
| Event_Enable | BACnetEventTransitionBits | O4,5 | no | no | An empty bit string. |
| Acked_Transitions | BACnetEventTransitionBits | O4,5 | no | no | An empty bit string. |
| Notify_Type | BACnetNotifyType | O4,5 | no | no | 0 |
| Event_Time_Stamps | BACnetARRAY[3] of BACnetTimeStamp | O4,5 | no | no | No default: the read fails. |
| Event_Message_Texts | BACnetARRAY[3] of CharacterString | O5,6 | no | no | "" |
| Event_Message_Texts_Config | BACnetARRAY[3] of CharacterString | O5 | no | no | "" |
| Event_Detection_Enable | Boolean | O4,5 | no | no | false |
| Reliability_Evaluation_Inhibit | Boolean | O | no | no | false |
| Property_List | BACnetARRAY[N] of BACnetPropertyIdentifier | R | yes | no | Held by the stack. |
| Value_Source | BACnetValueSource | O7,8,9 | no | no | No default: the read fails. |
| Audit_Level | BACnetAuditLevel | O10 | not in profile | not in profile | No default: the read fails. |
| Auditable_Operations | BACnetAuditOperationFlags | O10 | not in profile | not in profile | No default: the read fails. |
| Tags | BACnetARRAY[N] of BACnetNameValue | O | no | no | No default: the read fails. |
| Profile_Location | CharacterString | O | no | no | "" |
| Profile_Name | CharacterString | O | no | no | "" |